Single Core

High conductivity annealed stranded copper conductors to SANS 1411 Part 1. Insulated with PVC and skin coloured in plain colours to SANS 1411 Part 2. Cable is manufactured to SANS 1507 Part 2.

Description

Cable Size Nominal Stranding No. x diameter Approx. Overall Diameter Current Rating * Conductor Resistance @ 20°C Maximum 1φ Volt Drop Approx. Cable Mass per 100m Coil
(mm²) (mm) (A) (Ω/km) (mV/A/m) (kg)
1 7/0,42 3,0 17 18,1 43 1,7
1,5 7/0,53 3,3 21 12,1 29 2,2
2,5 7/0,66** 3,6 27 7,41 18 3,2
4 7/0,86** 4,5 36 4,61 11 5,2
6 7/1,04** 3,00 45 3,08 7,4 7,0
10 7/1,35** 6,0 61 1,83 4,4 11,1
16 7/1,67** 6,9 78 1,15 2,8 16,7

* Note

  • Rating based on two touching cables, installed in a duct.
  • Assumed ambient air temperature is 30°C.
  • Assumed maximum conductor temperature is 70°C.

** Note

  • Compacted conductors.

Additional information

Specification

SANS 1507-2

Temperature Range

-10°C to 70°C

Voltage Rating

600 / 1000V

Core Identification

Complete range of colours

Packaging

100m shrink-wrapped perforated coils / 500m reels